Zone 4 Seismic Cabinets

    Zone 4 Seismic Cabinets

      Product form

      Fully Welded 11-Gauge Steel Seismic Cabinets — 42RU to 48RU, 30″ to 48″ Depth, Bellcore GR-63-CORE Zone 4 Certified

      The Zone 4 Seismic Cabinets are fully welded 11-gauge (0.120″) cold rolled steel enclosures certified to Bellcore GR-63-CORE Section 4.4.1-2 for Zone 4 earthquake, office vibration, and transportation vibration environments. Available in 24 configurations across 42RU, 44RU, and 48RU heights with depths from 30″ to 48″, each cabinet is rated for 3,000 lbs static load capacity with seismic load ratings from 770 to 877 lbs depending on configuration. Certified to CSA C22.2 No. 70950-1 and compliant with EIA/ECA-310-E rack standards. Ships fully assembled with a 10-year warranty. Manufactured in Laval, Quebec.

          DESCRIPTIONDESCRIPTION

          Fully Welded 11-Gauge Steel Seismic Cabinets — 42RU to 48RU, 30″ to 48″ Depth, Bellcore GR-63-CORE Zone 4 Certified

          The Zone 4 Seismic Cabinets are fully welded 11-gauge (0.120″) cold rolled steel enclosures certified to Bellcore GR-63-CORE Section 4.4.1-2 for Zone 4 earthquake, office vibration, and transportation vibration environments. Available in 24 configurations across 42RU, 44RU, and 48RU heights with depths from 30″ to 48″, each cabinet is rated for 3,000 lbs static load capacity with seismic load ratings from 770 to 877 lbs depending on configuration. Certified to CSA C22.2 No. 70950-1 and compliant with EIA/ECA-310-E rack standards. Ships fully assembled with a 10-year warranty. Manufactured in Laval, Quebec.

          Server configurations (24″ wide) and network configurations (30″ wide) are available in matching height and depth options. Standard configuration includes a perforated front door, split perforated rear doors, four pairs of 1.25″ cage-nut mounting rails, a Universal Accessory Channel (UAC) for PDU integration, half-split lockable side panels, and a top cover with brush cable entry and provisions for heat exhaust chimney. Door options include solid, perforated, louvered, acrylic, split, thermal, and custom configurations. Cabinet must be floor-anchored using four seismic-rated anchors (not included). Available in black, white, or grey textured powder coat finish. Non-standard widths and depths available on request.

          KEY FEATURESKEY FEATURES

          Standard Configuration (Included with Every Cabinet)

          FEATURE ENGINEERING DETAIL
          Fully Welded 11-Gauge Frame 0.120″ cold rolled steel frame, fully welded construction. Rated for 3,000 lbs static load capacity. Seismic capacity from 770 to 877 lbs depending on model.
          Bellcore GR-63-CORE Zone 4 Certification Certified to GR-63-CORE Section 4.4.1-2 for Zone 4 earthquake environment, office vibration, and transportation vibration. Meets R4-83 (no permanent damage), R4-84 (deflection ≤3″), R4-85 (frequency >2.0 Hz), R4-87 (functional performance), and R4-90 (framework/anchor criteria).
          CSA C22.2 No. 70950-1 Safety Certification Electrical safety certification for information technology equipment enclosures.
          Four Pairs of 1.25″ Cage-Nut Mounting Rails EIA/ECA-310-E compliant rails with square holes and RU markings. Includes 50 heavy-duty 10-32 cage nuts and 50 matching 10-32 × 5/8″ screws.
          Perforated Front Door Full-height perforated steel door with lockable swing handle for airflow and security.
          Split Perforated Rear Doors Left-hand and right-hand perforated rear doors with lockable swing handles for rear access without full-width clearance.
          Half-Split Lockable Side Panels Four half-split side panels with locks for tool-free lateral access to cabling and equipment.
          Universal Accessory Channel (UAC) 6″-wide vertical cable management and accessory channel for PDU mounting and cable routing. Full cabinet height.
          Top Cover with Brush Cable Entry Solid top cover with brush-style cable entry provisions and two 6″ × 12″ cover plates for additional top cable routing.
          Heat Exhaust Chimney Provisions Top cover pre-configured for chimney integration. Compatible with Electron Metal containment solutions.
          4-Point Seismic Floor Anchoring Four anchor points at cabinet base for seismic-rated floor anchors. Anchors not included — must be specified for site conditions.
          Levelling Shims Eight levelling shims included for stability on uneven surfaces.
          Ships Fully Assembled Cabinet arrives fully assembled. No on-site frame assembly required.
          Textured Powder Coat Finish Available in black (-BK), white (-WH), or grey (-GY). Suffix appended to part number.

          Configuration Options

          OPTION DETAIL
          Width 24″ (server configuration, 19″ usable) or 30″ (network configuration, 25″ usable). Network configuration adds two front vertical cable management channels.
          Height 42RU (79.5″ overall), 44RU (83″ overall), or 48RU (90″ overall).
          Depth 30″, 36″, 42″, or 48″ overall depth. Usable depth is 1.25″ less than overall (28.75″, 34.75″, 40.75″, 46.75″).
          Door Options Solid, perforated (standard), louvered, acrylic, split, thermal, and custom configurations. Contact sales for non-standard door requests.
          Power & Thermal Enhancements Additional PDU mounting via UAC, fan integration through top cover provisions, chimney kits, and containment compatibility. Contact sales for configuration.
          SPECIFICATIONSSPECIFICATIONS

          Construction & Structural

          PARAMETER VALUE
          Frame Material 11-gauge (0.120″) cold rolled steel, fully welded
          Static Load Capacity 3,000 lbs
          Seismic Load Capacity 770–877 lbs (varies by configuration; see Available Configurations)
          Finish Textured powder coat
          Color Options Black (-BK), White (-WH), Grey (-GY)
          Weight Range (24″ Server) 337–444 lbs (verified from engineering drawings)
          Assembly State Ships fully assembled
          Warranty 10 years
          Manufacturing Origin Laval, Quebec, Canada

          Mounting & Access

          PARAMETER VALUE
          Rack Standard EIA/ECA-310-E, 19″ equipment width
          Mounting Rails Four pairs of 1.25″ cage-nut rails with square holes and RU markings
          Included Hardware 50× 10-32 heavy-duty cage nuts + 50× 10-32 × 5/8″ screws
          Front Door (Standard) Full-height perforated door with lockable swing handle
          Rear Doors (Standard) Split perforated doors (LH + RH) with lockable swing handles
          Side Panels Four half-split lockable side panels
          Floor Mounting 4-point seismic anchor system (seismic-rated anchors not included)
          Levelling 8 levelling shims included

          Cable & Thermal Management

          PARAMETER VALUE
          Vertical Cable Management Universal Accessory Channel (UAC), 6″ wide, full cabinet height
          Network Config Addition Two front vertical cable management channels (30″ width models only)
          Top Cable Entry Brush-style entry on top cover + two 6″ × 12″ cover plates
          Heat Exhaust Chimney Top cover pre-configured for chimney integration
          Fan Positions Provisions via top cover; fan kits available separately
          Containment Compatibility Compatible with Electron Metal hot and cold aisle containment solutions

          Certifications & Standards

          PARAMETER VALUE
          Seismic Certification Bellcore GR-63-CORE Section 4.4.1-2 — Zone 4 Earthquake Environment
          Safety Certification CSA C22.2 No. 70950-1
          Rack Standard EIA/ECA-310-E
          Physical Performance — R4-83 No permanent structural or mechanical damage
          Physical Performance — R4-84 Deflection not exceeding 3 inches
          Physical Performance — R4-85 Natural mechanical frequency greater than 2.0 Hz
          Functional Performance — R4-87 Equipment remains functional post-event
          Framework & Anchor — R4-90 Meets framework and anchor integrity criteria
          Design Reference TIA-942 data center infrastructure standard
          Manufacturing Origin Laval, Quebec, Canada
          Icon for filtersENGINEERING DETAILS
          Mechanical Design
          • Fully welded 11-gauge (0.120″) cold rolled steel frame — no bolted joints in primary structure
          • 3,000 lbs static load capacity across all configurations
          • Seismic load capacity ranges from 770 lbs (48RU × 48″D) to 877 lbs (42RU × 30″D) — capacity decreases with depth
          • 4-point seismic anchor base with 1″ mounting flange
          • Weight range: 337–444 lbs (24″ server configuration, verified from engineering drawings)
          • Half-split lockable side panels for lateral access without full panel removal
          Standards & Compliance
          • Bellcore GR-63-CORE Section 4.4.1-2 — Zone 4 earthquake, office vibration, transportation vibration
          • R4-83: No permanent structural or mechanical damage after Zone 4 seismic event
          • R4-84: Maximum deflection of 3 inches during event
          • R4-85: Natural mechanical frequency exceeds 2.0 Hz
          • R4-87: Equipment remains functional post-event
          • R4-90: Framework and anchor system meets integrity criteria
          • CSA C22.2 No. 70950-1 electrical safety certification
          • EIA/ECA-310-E rack mounting standard compliance
          Thermal & Airflow
          • Perforated front door and split perforated rear doors for passive airflow
          • Top cover with brush cable entry — maintains seal while allowing cable pass-through
          • Pre-configured provisions for heat exhaust chimney integration
          • Two 6″ × 12″ top cover plates for additional airflow or cable routing
          • Compatible with Electron Metal hot and cold aisle containment systems
          • Fan integration available through top cover provisions; fan kits sold separately
          Cable & Power Integration
          • Universal Accessory Channel (UAC): 6″-wide vertical channel, full cabinet height, for PDU and cable routing
          • Four pairs of 1.25″ cage-nut mounting rails with EIA/ECA-310-E square holes and RU markings
          • 50 heavy-duty 10-32 cage nuts and 50 matching 10-32 × 5/8″ screws included
          • Network configuration (30″ width) adds two front vertical cable management channels
          • Brush-style top cable entry on all configurations
          • Two additional 6″ × 12″ top cable entry points with removable cover plates

          Custom Options

          Custom & Non-Standard Configurations
          • Non-standard widths and depths available on request
          • Custom door configurations: solid, louvered, acrylic, thermal, split, and application-specific designs
          • Additional power distribution options via UAC channel
          • Chimney kits for directed exhaust in containment environments
          • Color matching and custom powder coat finishes
          • Project-specific seismic engineering support — contact sales@electronmetal.ca
          Icon for questionMORE CONTENT

          Server Configuration (24″ Width)

          All dimensions in inches (W × H × D). 11-gauge fully welded cold rolled steel frame. 3,000 lbs static load capacity. Ships fully assembled. Weight and seismic capacity verified from engineering drawings.

          MODEL RU OVERALL DIMENSIONS
          W × H × D
          USABLE DIMENSIONS
          W × RU × D
          DEPTH WEIGHT
          lbs
          SEISMIC CAP.
          lbs
          CBZKI4-194230 42 24 × 79.5 × 30 19 × 73.5 × 28.75 30″ 337 877
          CBZKI4-194236 42 24 × 79.5 × 36 19 × 73.5 × 34.75 36″ 361 853
          CBZKI4-194242 42 24 × 79.5 × 42 19 × 73.5 × 40.75 42″ 386 828
          CBZKI4-194248 42 24 × 79.5 × 48 19 × 73.5 × 46.75 48″ 410.8 803.2
          CBZKI4-194430 44 24 × 83 × 30 19 × 77 × 28.75 30″ 342 872
          CBZKI4-194436 44 24 × 83 × 36 19 × 77 × 34.75 36″ 368 846
          CBZKI4-194442 44 24 × 83 × 42 19 × 77 × 40.75 42″ 393.5 820.5
          CBZKI4-194448 44 24 × 83 × 48 19 × 77 × 46.75 48″ 419 795
          CBZKI4-194830 48 24 × 90 × 30 19 × 84 × 28.75 30″ 364 850
          CBZKI4-194836 48 24 × 90 × 36 19 × 84 × 34.75 36″ 391 823
          CBZKI4-194842 48 24 × 90 × 42 19 × 84 × 40.75 42″ 417 797
          CBZKI4-194848 48 24 × 90 × 48 19 × 84 × 44.75 48″ 444 770

          Network Configuration (30″ Width)

          All dimensions in inches (W × H × D). Includes two front vertical cable management channels. Engineering drawings not provided for network configuration — weight and seismic capacity data unavailable.

          MODEL RU OVERALL DIMENSIONS
          W × H × D
          USABLE DIMENSIONS
          W × RU × D
          DEPTH
          CBZKI4-254230 42 30 × 79.5 × 30 25 × 79.5 × 28.75 30″
          CBZKI4-254236 42 30 × 79.5 × 36 25 × 79.5 × 34.75 36″
          CBZKI4-254242 42 30 × 79.5 × 42 25 × 79.5 × 40.75 42″
          CBZKI4-254248 42 30 × 79.5 × 48 25 × 79.5 × 46.75 48″
          CBZKI4-254430 44 30 × 83 × 30 25 × 83 × 28.75 30″
          CBZKI4-254436 44 30 × 83 × 36 25 × 83 × 34.75 36″
          CBZKI4-254442 44 30 × 83 × 42 25 × 83 × 40.75 42″
          CBZKI4-254448 44 30 × 83 × 48 25 × 83 × 46.75 48″
          CBZKI4-254830 48 30 × 90 × 30 25 × 90 × 28.75 30″
          CBZKI4-254836 48 30 × 90 × 36 25 × 90 × 34.75 36″
          CBZKI4-254842 48 30 × 90 × 42 25 × 90 × 40.75 42″
          CBZKI4-254848 48 30 × 90 × 48 25 × 90 × 46.75 48″